Inspection
Inspection Details
Equipment ID
18774
18774
Inspection Date
1/23/2019
1/23/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
630
630
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
a4f67529-540c-4d32-985d-8397747f454a
a4f67529-540c-4d32-985d-8397747f454a
Location
Lumiere Place Casino
999 N 2ND ST, SAINT LOUIS, MO
999 N 2ND ST, SAINT LOUIS, MO
Owner
Attn: Dwight Buchannon
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Four Seasons Hotel
999 N 2ND ST, SAINT LOUIS, MO 63102
Phone: (314) 498-8304
Email: dwight.buchannon@fourseasons.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | No | No | Repair drywall around oil line. | 12/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform test on or before next annual inspection date. | 4/26/2021 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Repair drywall around oil line. | 12/7/2025 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Remove or cut the roofing nail tips flush that are protruding through the top of the hoistway. | 12/7/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 1/9/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/7/2025 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Remove or cut the roofing nail tips flush that are protruding through the top of the hoistway | 12/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly, needs repaired or replaced. Re-inspection required | 1/2/2025 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Remove or cut the roofing nail tips flush that are protruding through the top of the hoistway. | 12/7/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair / replace this phone for proper operation and passenger safety. Re-inspection required | 12/7/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) | Yes | No | Phase 1 Fire Service light not working on hall keyswitch |