Inspection
Inspection Details
Equipment ID
7965
7965
Inspection Date
2/11/2026
2/11/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Dennis Smith
Dennis Smith
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
/A
/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
0a9a8057-9581-448d-b78f-097efe6bba6f
0a9a8057-9581-448d-b78f-097efe6bba6f
Location
Buchanan County Courthouse
411 Jules St, St. Joseph, MO
Phone: (816) 271-1419
411 Jules St, St. Joseph, MO
Phone: (816) 271-1419
Owner
Attn: Kim Hartman
Buchanan, County of
411 Jules St, St. Joseph, MO 64501
Phone: (816) 271-1512
Email: khartman@co.buchanan.mo.us
Buchanan, County of
411 Jules St, St. Joseph, MO 64501
Phone: (816) 271-1512
Email: khartman@co.buchanan.mo.us
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Permit needs to be obtained from the state for replacement of hydraulic pumping unit, which has already been replaced. | 1/30/2019 |
| conversion | conversion | conversion - red tag | Yes | Yes | Replaced pumping unit needs acceptance test performed and witnessed by a licensed inspector.. | 1/30/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking. | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove non-elevator related material and rags from machine room floor. | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Install front cover on motor controller enclosure. | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Provide firefighter key on site | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire Do Not Use Elevator signage next to corridor call station | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire recall | 1/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove standing water and oil from pit floor | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Attach metal test tag for periodic test | 1/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Install cover on starter panel in machine room | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Firefighter key needs to be kept on site | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | No visual signal during fire recall operation | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Maintenance record log not up to date | 2/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 2/11/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Phase 1 jewel on COP not working. | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Provide a cover for starter panel in machine room. | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | EMERGENCY LIGHT NOT WORKING | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | REPACK JACK AND CLEAN OIL OVERFLOW FROM PIT | 2/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | FASTEN SPRING STANDS DOWN TO PIT CHANNEL | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | INSTALL COVER ON STARTER PANEL | 2/11/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | PROVIDE A WORKING IN CAR FIRE SERVICE JEWEL | 2/11/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE A WORKING EMERGENCY LIGHT & ALARM | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | PROVIDE A WORKING PHASE 1 FIRE SERVICE JEWEL |