Inspection
Inspection Details
Equipment ID
575
575
Inspection Date
1/30/2026
1/30/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Paul Bartlett
Paul Bartlett
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
f943ca36-b907-4313-9e5f-e79106a52a34
f943ca36-b907-4313-9e5f-e79106a52a34
Location
Palen Music Center
1560 E Raynell Pl, Springfield, MO
Phone: (417) 447-3540
Email: accountspayable@palenmusic.com
1560 E Raynell Pl, Springfield, MO
Phone: (417) 447-3540
Email: accountspayable@palenmusic.com
Owner
Attn: Palen Music Co
Palen Music Co
1560 E Raynell Pl, Springfield, MO 65804
Phone: (417) 447-3540
Fax: (417) 882-7006
Email: accounting@palenmusic.com
Palen Music Co
1560 E Raynell Pl, Springfield, MO 65804
Phone: (417) 447-3540
Fax: (417) 882-7006
Email: accounting@palenmusic.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed | 3/10/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pump located in pit required to be removed | 2/15/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)9 | No | No | Could not check could not fined key | 2/15/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 2/15/2026 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Must make Emergency Light operable. | 8/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | NO Records | 2/15/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 2/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No records | 2/15/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 2/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Must make pit light operable | 2/15/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | Must provide and maintain MCP documents and logs | 2/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Must make Pit Light operable. | 3/2/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | Must provide and Maintain all required MCP Documents and Logs. 8.6.1.4 | 3/2/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Must provide current annual test tag on mach. room Fire Extinguisher. 8.6.1.6.5 | 3/2/2026 |
| A17.1-2016 : Elevators | 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) | 8.6.4.19.6 | Yes | No | Fire Service must be tested monthly and documented. 8.6.4.19.6 | 3/2/2026 |