Inspection
Inspection Details
Equipment ID
19225
19225
Inspection Date
1/25/2019
1/25/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
370
370
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
0601ab1b-5f8d-4ef5-b668-66c92e1bc603
0601ab1b-5f8d-4ef5-b668-66c92e1bc603
Location
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO
4300 DUNCAN AVE, SAINT LOUIS, MO
Owner
Attn: UNK
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Billing
Attn: Du Pont
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: christopher.nash@am.jll.com
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: christopher.nash@am.jll.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Place state operating certificate in machine room. | 3/4/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV not tagged or sealed. Perform OSV test on or before next annual inspection. | 1/24/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work, phone line appears dead. Re-inspection required | 1/26/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. Phone line appears dead | 12/21/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 7/15/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Replace any missing fire tabs on hoistway doors. | 7/15/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Replace faded/damaged Phase 2 fire service instructions. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on the emergency generator. Take corrective action and re-test. | 12/13/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | Replace any missing fire tabs on hoistway doors. | 12/13/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on the emergency generator. Take corrective action and re-test. (2nd Notice) | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | Replace missing fire tabs on hoistway doors. (2nd Notice) |