Inspection
Inspection Details
Equipment ID
26897
26897
Inspection Date
2/19/2026
2/19/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
450
450
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
15
15
External ID
6392d6c3-5e1e-4ca7-a609-549bebc44a47
6392d6c3-5e1e-4ca7-a609-549bebc44a47
Location
Best Box
1440 Prospect Rd, Lake St. Louis, MO
Phone: (314) 302-5431
Email: nscheer@dss-bcm.com
1440 Prospect Rd, Lake St. Louis, MO
Phone: (314) 302-5431
Email: nscheer@dss-bcm.com
Owner
Attn: Accounts Payable
Best Box Lake St. Louis, MO Prospect, LLC
222 S Central Ave Ste 305, Saint Louis, MO 63105
Phone: (314) 302-5431
Email: AP@bestboxstorage.com
Best Box Lake St. Louis, MO Prospect, LLC
222 S Central Ave Ste 305, Saint Louis, MO 63105
Phone: (314) 302-5431
Email: AP@bestboxstorage.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | Yes | No | The overhead fasteners protruding through the ceiling of the overhead shall be cut flush to prevent a hazardous situation. | 3/18/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | In electrical equipment rooms, the illumination shall not be controlled by automatic means only. Note: The machine room light shall remain on anytime the switch is in the on position. | 3/18/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | Spot-type smoke detectors shall be located on the ceiling or, if on a sidewall, between the ceiling and 12 inches down from the ceiling to the top of the detector. Note: The smoke detector in the overhead does not meet these requirements. | 3/18/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | All electrical boxes in the machine room shall have covers installed and any knockout holes shall be plugged. | 3/18/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Separate branch circuits shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter. | 3/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | A clear distance of not less than 4.5 inches from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the pit ladder shall be provided. | 3/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.2 | Yes | No | The pit floor shall be flush. Note: The sump pump grate is protruding from the surface floor creating a potential tripping hazard. This shall be corrected. | 3/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | The pit lighting shall provided an illumination of not less than 10 foot-candles at the pit floor. | 3/18/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Mineral wool shall be installed in the overhead where the ceiling meets the wall per Fire Marshall. | 3/18/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | On elevators provided with firefighters' emergency operation, a drain or sump pump shall be provided. the sump pump/drain shall have the capacity to remove a minimum of 3,000 gal/h per elevator. Note: The sump pump provided doesn't appear to meet this requirement after calculating for dynamic head. A higher capacity pump shall be provided. | 3/18/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Separate branch circuits shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter. | 4/16/2025 |