Inspection
Inspection Details
Equipment ID
18711
18711
Inspection Date
2/12/2026
2/12/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
f695febd-0027-4864-b14a-ea45de9cfa52
f695febd-0027-4864-b14a-ea45de9cfa52
Location
Chesterfield Business Parkway
100 Chesterfield Business Pkwy, Chesterfield, MO
Phone: (636) 728-5163
100 Chesterfield Business Pkwy, Chesterfield, MO
Phone: (636) 728-5163
Owner
Attn: Joshua M. Coffman
Land West #7 LLC c/o Trident Group
17998 Chesterfield Airport Rd, Ste 200, Chesterfield, MO 63005
Phone: (636) 449-2600 Ext: 12
Alt Phone: (314) 744-1661
Email: josh@ustrident.com
Land West #7 LLC c/o Trident Group
17998 Chesterfield Airport Rd, Ste 200, Chesterfield, MO 63005
Phone: (636) 449-2600 Ext: 12
Alt Phone: (314) 744-1661
Email: josh@ustrident.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform OSV test on or before next annual inspection. | 6/4/2021 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Battery backup lowering unit not working correctly, repair/replace as needed. | 5/2/2023 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 302.3 | No | No | Provide pit bucket. | 2/20/2026 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | No | No | Remove scavenger line from tank. | 2/20/2026 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | No | No | Remove scavenger pump unit from pit. | 2/20/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 2/20/2026 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | Unsealed. | 5/2/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed or tagged. Shall be tested within 30 days. | 2/20/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Emergency lowering device shall be made operational. Re-inspection required | 6/17/2024 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | There shall be a switch in the disconnect that will not activate the emergency lowering device when the disconnect is turned off | 2/20/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency lowering device is not working. Re-inspection required | 3/31/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | There shall be a switch in the disconnect that will not activate the emergency lowering device when the disconnect is turned off. Re-inspection required | 3/31/2025 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | Yes | No | Remove scavenger line from the tank. | 2/20/2026 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | Yes | No | Remove scavenger unit from the pit. | 2/20/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide existing battery backup lowering unit to work properly. | 2/20/2026 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Cylinder head packing is worn and leaking, repair as needed. | 2/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/13/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide existing battery backup lowering unit to work properly. | 4/6/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide existing battery backup lowering unit to work properly. |