Inspection
Inspection Details
Equipment ID
19224
19224
Inspection Date
1/25/2019
1/25/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
d2481073-49d1-4f37-9eab-03601ded98d1
d2481073-49d1-4f37-9eab-03601ded98d1
Location
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO
4300 DUNCAN AVE, SAINT LOUIS, MO
Owner
Attn: UNK
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Billing
Attn: Du Pont
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: christopher.nash@am.jll.com
Du Pont
4300 DUNCAN AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: christopher.nash@am.jll.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Place state certificate in machine room. | 3/4/2019 | ||
| conversion | conversion | conversion - reinspect | x | Phone in elevator cab does not work. Repair. | 8/6/2018 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV not tagged or sealed. Perform OSV test on or before next annual inspection. | 1/24/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work as intended. Phone dials out then goes to a busy/disconnected signal. Repair or replace | 12/21/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 7/15/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/24/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on the emergency generator. Take corrective action and re-test. | 12/13/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/24/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on the emergency generator. Take corrective action and re-test. (2nd Notice) | 2/24/2026 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Pits shall be kept clean, dry, and free of debris and oil. | 2/24/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on the emergency generator. Take corrective action and re-test | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.14.1.7 Railing and Equipment on Top of Cars | handrail system shall be installed on car top. Distance is greater than 12 inches from car top to hoistway wall. |