Inspection
Inspection Details
Equipment ID
5560
5560
Inspection Date
1/25/2019
1/25/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
16 in.
16 in.
Governor Rope Pull
85/740
85/740
Door Closing Force
20
20
External ID
94fb1433-a021-4eb7-ba6a-0c25bfd88be6
94fb1433-a021-4eb7-ba6a-0c25bfd88be6
Location
Lindell Terrace Condo
4501 LINDELL BLVD, SAINT LOUIS, MO
4501 LINDELL BLVD, SAINT LOUIS, MO
Owner
Lindell Terrace Condo Assn
4501 LINDELL BLVD, SAINT LOUIS, MO 63108-1846
4501 LINDELL BLVD, SAINT LOUIS, MO 63108-1846
Billing
Attn: Lindell Terrace Condo
4501 LINDELL BLVD, SAINT LOUIS, MO 63108-1846
4501 LINDELL BLVD, SAINT LOUIS, MO 63108-1846
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work. Phone line dead to controller. | 7/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | ASME A17.2-1.5 ASME A17.1 2004 with 2005 Supplement 8.6.4.15 The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 3/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | ASME A17.2-1.6 ASME A17.1 2004 with 2005 Supplement 8.11.2.1.1 (f) When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 3/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | Phase II fire service does not work. Repair and reinspect no later than 2/26/21. | 4/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency generator power, which needs to be scheduled and tested to complete inspection. Re-inspection required | 4/22/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 2/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Need to prevent water intrusion into the machinery / control space. Water is leaking on the rope gripper, need to seal where water is getting entering machine room | 2/3/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Failed Cat 1 Standby power test. Generator would not switch over to emergency power. Re-inspection required | 2/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Hoistway door retainers are required on all doors | 5/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.1.3.3 | No | No | Prevent water intrusion into the machine/control room/space. Water is leaking on the rope .gripper seal | 5/21/2026 |