Inspection
Inspection Details
Equipment ID
15066
15066
Inspection Date
3/2/2026
3/2/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
5e735ca1-3d31-44f6-a1d0-766fd026adca
5e735ca1-3d31-44f6-a1d0-766fd026adca
Location
Crestwood Professional Building
9201 Watson Rd, St. Louis, MO
Phone: (314) 919-2016
9201 Watson Rd, St. Louis, MO
Phone: (314) 919-2016
Owner
Attn: Crestwood Professional Building
Crestwood Professional Building
9201 Watson Rd, Ste 300, St. Louis, MO 63126
Phone: (314) 919-2016
Crestwood Professional Building
9201 Watson Rd, Ste 300, St. Louis, MO 63126
Phone: (314) 919-2016
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 12/7/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/7/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. | 8/26/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. | 12/14/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/22/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. The tag is expired. | 1/22/2026 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 1/22/2026 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | Yes | No | The wireless phone line device and wiring shall be installed so it does not block access to the elevator equipment. | 1/22/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 3/4/2026 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Elevator must be fitted with permanent flooring. | 3/4/2026 |