Inspection
Inspection Details
Equipment ID
16571
16571
Inspection Date
2/24/2026
2/24/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
660
660
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
9b56b0b8-8af7-4350-afe1-095e8bac306c
9b56b0b8-8af7-4350-afe1-095e8bac306c
Location
Des Peres Community Center
1050 Des Peres Rd, Des Peres, MO
Phone: (636) 541-9648
1050 Des Peres Rd, Des Peres, MO
Phone: (636) 541-9648
Owner
Attn: Des Peres
City of Des Peres
1050 Des Peres Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: cnewgent@desperesmo.org
City of Des Peres
1050 Des Peres Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: cnewgent@desperesmo.org
Billing
Attn: Des Peres
City of Des Peres
1050 Des Peres Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: jlewis@desperesmo.org
City of Des Peres
1050 Des Peres Rd, Des Peres, MO 63131
Phone: (314) 835-6111
Email: jlewis@desperesmo.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/21/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 11/23/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 11/23/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/23/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. | 11/10/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/4/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 3/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The fire service phase one key-switch bezel shall be legible. | 3/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The fire service phase two key-switch bezel shall be legible. | 3/4/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | MERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER(battery is low and 1 of 2 lamps is not working). | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | The fire service phase one key-switch bezel shall be legible. REPEAT VIOLATION | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | he fire service phase two key-switch bezel shall be legible. REPEAT VIOLATION | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site |