Inspection
Inspection Details
Equipment ID
26656
26656
Inspection Date
2/27/2026
2/27/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
2670a445-af21-4ad1-a3c6-58cd168ecc04
2670a445-af21-4ad1-a3c6-58cd168ecc04
Location
New Perspective Senior Living
400 Siedentop Rd, Weldon Springs, MO
Phone: (608) 664-3625
Email: justin.dall'osto@iconicacreates.com
400 Siedentop Rd, Weldon Springs, MO
Phone: (608) 664-3625
Email: justin.dall'osto@iconicacreates.com
Owner
Attn: Weldon Springs RE, LLC
Weldon Springs RE, LLC
1110 N Dr Martin Luther King Jr Dr, Milwaukee, WI 53203
Phone: (000) 000-0000
Weldon Springs RE, LLC
1110 N Dr Martin Luther King Jr Dr, Milwaukee, WI 53203
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency power operation shall be tested, with weights. | 9/18/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | x | Emergency power jewel needs to be installed at main landing. | 9/18/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Machine room floor drain is creating a tripping hazard and shall be flush to the floor or removed. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | 1 of 2 machine room lights are not working. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Machine room: Overhead thru piping and flex shall be removed or enclosed. | 9/18/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Disconnects need feed location labels. | 9/18/2024 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Hoistway fire penetrations need to be fire caulked. | 9/18/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | x | Secure sump pump cover. | 9/18/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Light switch next to rear pit light needs to be removed. | 9/18/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | x | The pit shall be kept clean and free of dirt and debris. | 9/18/2024 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 3.8 | x | Install cover or remove unused single gang electrical box in pit. | 9/18/2024 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Fire caulk pit fire penetrations. | 9/18/2024 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Need to test all FAID operations. | 9/18/2024 |