Inspection
Inspection Details
Equipment ID
26657
26657
Inspection Date
2/27/2026
2/27/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14
14
External ID
6dcc1067-a196-48c6-a82b-f856bf3ef55a
6dcc1067-a196-48c6-a82b-f856bf3ef55a
Location
New Perspective Senior Living
400 Siedentop Rd, Weldon Springs, MO
Phone: (608) 664-3625
Email: justin.dall'osto@iconicacreates.com
400 Siedentop Rd, Weldon Springs, MO
Phone: (608) 664-3625
Email: justin.dall'osto@iconicacreates.com
Owner
Attn: Weldon Springs RE, LLC
Weldon Springs RE, LLC
1110 N Dr Martin Luther King Jr Dr, Milwaukee, WI 53203
Phone: (000) 000-0000
Weldon Springs RE, LLC
1110 N Dr Martin Luther King Jr Dr, Milwaukee, WI 53203
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Car phone does not work. | 9/18/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency power operation shall be tested, with weights. | 9/18/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | x | Emergency power jewel needs to be installed at main landing. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | x | The machine room door is missing most of the fire gasket material. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | There is no light switch and no GFI outlet in the machine room. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | x | Walls to be of solid construction, fill fire penetrations, cracks, and gaps. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | x | FAID devices to be permanently installed with appropriate covers. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Machine room: Overhead water/waste piping not allowed in machine space. | 9/18/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Disconnects need feed location labels. | 9/18/2024 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Disconnect to controller "flex" shall not exceed 6ft in length. | 9/18/2024 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Hoistway fire penetrations need to be fire caulked. | 9/18/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | x | Secure sump pump cover. | 9/18/2024 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 3.8 | x | Sump outlet shall be a single outlet, not duplex. | 9/18/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Pit lighting shall be at least 10fc. | 9/18/2024 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Need to test all FAID operations. | 9/18/2024 |