Inspection
Inspection Details
Equipment ID
18573
18573
Inspection Date
2/16/2026
2/16/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
d0972db4-713c-414b-bec7-9cfa7114a8b3
d0972db4-713c-414b-bec7-9cfa7114a8b3
Location
4545 Lindell
4545 Lindell Blvd, St. Louis, MO
Phone: (314) 361-8260
Email: ABelsky@rcirealty.com
4545 Lindell Blvd, St. Louis, MO
Phone: (314) 361-8260
Email: ABelsky@rcirealty.com
Owner
Attn: Rodemeyer Christel Inc
4545 Lindell A Condominium
3630 Grandel SQ, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 318
Email: ABelsky@rcirealty.com
4545 Lindell A Condominium
3630 Grandel SQ, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 318
Email: ABelsky@rcirealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program needs to include testing procedures | 12/6/2020 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | No | No | Water line for outside faucet is not allowed in machine room | 12/6/2020 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | No | No | Where water line goes through wall in machine room, the fire rated assembly has been compromised | 12/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Need testing procedures included in MCP on or before January 1, 2022 | 12/4/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | No | No | Service Fire Extinguisher in machine room 8.6.1.6.5 | 12/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 12/21/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test & document on log in machine room | 12/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Provide a complete maintenance control plan to include testing procedures | 12/21/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 12/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 12/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 11/12/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in the machine room | 11/12/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testb emergency generator | 11/12/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Service fire extinguisher in the machine room | 11/12/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Perform Monthly Fire Service and Document on Log Posted in Machine Room | 3/2/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post Current Certificate in The Machine Room | 3/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test Emergency Generator (Reinspection Required within 30 days ) | 3/2/2026 |