Inspection
Inspection Details
Equipment ID
22169
22169
Inspection Date
3/5/2026
3/5/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
1300
1300
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
24
24
External ID
2c911bf8-42d8-4668-abfd-1369172be1b5
2c911bf8-42d8-4668-abfd-1369172be1b5
Location
Mann Elementary School
4047 Juniata St, St. Louis, MO
Phone: (314) 565-6747
4047 Juniata St, St. Louis, MO
Phone: (314) 565-6747
Owner
Attn: Anthony Graphenreed
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Anthony.Graphenreed@slps.org
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Anthony.Graphenreed@slps.org
Billing
Attn: Cardinal Elevator
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: Anthony.Graphenreed@slps.org
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: Anthony.Graphenreed@slps.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | No | No | Machine room shall not be used for storage of non-elevator related materials. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | An ABC type fire extinguisher is required in the machine room. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.14 - Supply Piping | 8.11.3.1.5(i) | No | No | Correct slight leak at rupture valve. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.14 - Supply Piping | 8.11.3.1.5(i) | No | No | There is no rating on the oil supply line. Confirm if proper piping has been used. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The machine room shall not be used for the storage of non-elevator related items. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide a code compliant fire extinguisher in the machine room. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.32 - Control Valve | 3.19.4.7.1 Overspeed Valve Test | Yes | No | Correct the slight leak at the rupture valve. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.14 - Supply Piping | 8.11.3.1.5(i) | No | No | There is no rating on the oil supply line. Confirm if proper piping has been used. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 3/23/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken- suspension-member detection means, residual-strength detection means, and related circuits. These procedures would have had to be present for previous inspections to have been performed but are not located at this facility currently. | 3/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | A readable set of controller wiring blue prints shall be available in the machine room to perform maintenance and inspection. These blue prints would have been available when the elevator was installed but are not currently located at this facility. | 3/10/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The relief valve pressure test performed, and car safeties set before the inspection is completed. Reinspection required. | 3/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | Door force exceeds Code, adjust as needed. | 3/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.34 - Flexible Hydraulic Hose and Fitting Assemblies | 8.11.3.1.2 (q) | No | No | Flex hose stamped 4000 psi. Code requires hose rated bursting strength 10x working pressure. 3.19.3.3.1. Repair as needed. | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Existing phone not working correctly, repair as needed. | 3/23/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Perform the required Cat 5 testing on the Overspeed Valve | 2/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | No | No | Elevator equipment shall be separated from the storage by a 1hr rated wall with a self closing self locking class C door or removed from the room | 3/10/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | No | No | Remove all non elevator related items from the elevator machine room. | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Provide existing battery backup lowering unit to work. | 7/23/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 3.19.4.7.5(a) | No | No | OSV testing failed, repair/replace as needed. | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Post current State Elevator Certificate. | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | Yes | No | Remove all non elevator related items from the elevator machine room. | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide existing battery backup lowering unit to work properly. | 3/5/2026 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Provide testing on OSV. | 3/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | Yes | No | Provide updated prints. | 3/5/2026 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 3.19.4.7.5(a) | No | No | Overspeed Valve is due for testing. |