Inspection
Inspection Details
Equipment ID
21487
21487
Inspection Date
3/6/2026
3/6/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
1500
1500
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
25
25
External ID
05c9b369-2717-47c2-b003-25ec18a41f7c
05c9b369-2717-47c2-b003-25ec18a41f7c
Location
Buder Elementary School
5319 Lansdowne Ave, St. Louis, MO
Phone: (314) 581-0223
Email: anthony.graphenreed@slps.org
5319 Lansdowne Ave, St. Louis, MO
Phone: (314) 581-0223
Email: anthony.graphenreed@slps.org
Owner
Attn: Rashad Sullivan
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 940-1724
Email: RashadSullivan@slps.org
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 940-1724
Email: RashadSullivan@slps.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The fire extinguisher in the machine room is expired. | 2/1/2021 |
| conversion | conversion | n/a | No | No | Remove all non-elevator related equipment from the elevator machine room. | 2/1/2021 |
| conversion | conversion | n/a | No | No | Sump hole in the pit shall be covered. | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | Yes | No | The low pressure switch shall be operational. | 7/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | The pit sump pump hole shall have a cover installed. | 2/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | No | No | Pressure switch inoperable | 1/19/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | Yes | No | Pressure switch inoperable. Re-inspection required | 1/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Replace missing hoistway door gibb at 2nd floor landing. Re-inspection required | 2/19/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Auxiliary battery lowering device (emergency recue unit) does not work, needs repaired. Re-inspection required | 2/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform relief valve system pressure test. Re-inspection required | 2/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The relief pressure test shall be performed and safeties set before the inspection is completed. The maintenance provider shall have the proper equipment to complete test. | 3/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 3/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | 3/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | 6/3/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. |