Inspection
Inspection Details
Equipment ID
9380
9380
Inspection Date
3/11/2026
3/11/2026
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
420
420
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15/15
15/15
External ID
576d3f8f-ff3f-43de-beb7-a972f07a37f0
576d3f8f-ff3f-43de-beb7-a972f07a37f0
Location
West County Center
80 W COUNTY CTR, SAINT LOUIS, MO
Phone: (314) 288-2020
80 W COUNTY CTR, SAINT LOUIS, MO
Phone: (314) 288-2020
Owner
Attn: Andrew Goldacker
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post Mo Stae certificate in machine room | 10/22/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 10/22/2019 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | Machine room needs to be locked at all times. | 10/22/2019 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Top level door is missing two door gibs. | 10/22/2019 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 210.1e | No | No | Gate switch exceeds minimum measurement for center opening doors. Reinspect. | 10/22/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | There needs to be a working lit in the pit. | 10/22/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light not working. | 11/20/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell not working. | 11/20/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 10/22/2019 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | No | Yes | Adjust car door to cab clearance to 3/8 max - currently in excess of 1/2 inch. | 9/28/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Replace missing door gibbs on 5th floor and missing fire tab on 3rd floor. | 9/28/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Annual tag shows expired. | 11/30/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work on 110v emergency power or normal power | 4/9/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light in the cab does not work | 4/9/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Provide existing pit light to work. | 3/13/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 3/13/2026 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Provide car top light to work. | 3/13/2026 |
| A17.1-1996 : Elevators | 3.8 - Top emergency exit | 204.1e | No | No | Provide means to secure car top exit. | 3/13/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Provide,on Phase II operations, call cancel feature to work. | 4/17/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1202.5 | Yes | No | Observed tile floor needs to be secured down or replaced. |