Inspection
Inspection Details
Equipment ID
14978
14978
Inspection Date
3/12/2026
3/12/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
300
300
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
3059f8c2-9039-4604-9fc2-e3b861911313
3059f8c2-9039-4604-9fc2-e3b861911313
Location
Best Western Plus
2621 E 5th St, Washington, MO
Phone: (636) 390-8877
2621 E 5th St, Washington, MO
Phone: (636) 390-8877
Owner
Attn: Narayandas LLC
Narayandas LLC
2621 E 5th St, Washington, MO 63090
Phone: (000) 000-0000
Email: ashok1016@yahoo.com
Narayandas LLC
2621 E 5th St, Washington, MO 63090
Phone: (000) 000-0000
Email: ashok1016@yahoo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Pit shall be kept clean and dry. | 3/6/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit shall be kept clean and dry. | 3/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 3/30/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 3/25/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform test on or before next annual inspection. | 3/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2 way communication is not working, Re-inspection required | 2/28/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post Phase I instructions in lobby, near f/f switch. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide working pit light. | 8/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Piston packing worn and leaking, repair as needed. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Determine if the sump pump works properly, if not replace. | 8/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Provide means to prevent ground water from entering the pit. To prevent rusting of pit equipment. | 8/14/2025 |