Inspection
Inspection Details
Equipment ID
10879
10879
Inspection Date
3/16/2026
3/16/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
25 lbs
25 lbs
External ID
e2fbbc1b-b540-496c-9660-6dc63b549f3c
e2fbbc1b-b540-496c-9660-6dc63b549f3c
Location
Monogram Building
1706 Washington Ave, St. Louis, MO
Phone: (314) 707-9802
1706 Washington Ave, St. Louis, MO
Phone: (314) 707-9802
Owner
Attn: Monogram Building LLC
Monogram Building LLC
1706 Washington Ave, St. Louis, MO 63103
Phone: (314) 357-2626
Email: manager@livemonogramstl.com
Monogram Building LLC
1706 Washington Ave, St. Louis, MO 63103
Phone: (314) 357-2626
Email: manager@livemonogramstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of the elevator on emergency power. | 8/4/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of the existing emergency power selector switch, located in the elevator machine room. | 8/4/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase I operations, record results. | 8/4/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase II operations, record results. | 8/4/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Existing car top light switch not working, repair/replace as needed. | 11/20/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Remove mounted paper towel dispenser from the elevator. | 11/20/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of the existing emergency power selector switch, located in the elevator machine room | 12/12/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Remove mounted paper towel dispenser from the elevator | 11/20/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform Monthly Fire Service Test and Document on the Log posted in the Machine Room | 3/31/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post Current State Certificate in the Machine Room | 3/31/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair Emergency Bell in Car (Battery Backup) | 10/15/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Reinspection Tested Emergency Bell in the Bell - Failed | 3/17/2026 |