Inspection
Inspection Details
Equipment ID
14756
14756
Inspection Date
3/10/2026
3/10/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
340
340
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
b0884fb7-b986-4e43-abf5-0a5094b0d7a1
b0884fb7-b986-4e43-abf5-0a5094b0d7a1
Location
Arcaidia Valley Medical
200 Saint Mary St, Pilot Knob, MO
Phone: (573) 546-3084
200 Saint Mary St, Pilot Knob, MO
Phone: (573) 546-3084
Owner
Attn: Carl Strange
The Oppel Strange Foundation
PO BOX 166, Ironton, MO 63650
Phone: (573) 999-1145
The Oppel Strange Foundation
PO BOX 166, Ironton, MO 63650
Phone: (573) 999-1145
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | No | No | Need maintenance control program. A17.2.2.41 | 6/16/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. | 6/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance records in machine room. | 6/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current tested fire extinguisher in the elevator machine room. | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Cylinder packing is worn and leaking, repair as needed. | 3/17/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit.(water/oil) | 3/17/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Provide means to prevent the accumulation of groundwater in the pit. Rust prevention of pit equipment needed. | 3/17/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone is not working. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The is no fire extinguisher in the machine room | 3/17/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from the pit | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Smoke detector is hanging down from machine room ceiling. | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Phone is not working in the elevator. Re-inspection required | 3/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The is no fire extinguisher in the machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from the pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Smoke detector is hanging down from machine room ceiling. |