Inspection
Inspection Details
Equipment ID
16887
16887
Inspection Date
2/9/2026
2/9/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Anderson
James Anderson
Mechanic Name
Nathaniel Smith
Nathaniel Smith
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
e39f44a0-38fa-481c-8f31-2977464616c0
e39f44a0-38fa-481c-8f31-2977464616c0
Location
St. Louis Busch Stadium
700 Clark Ave, St. Louis, MO
Phone: (314) 345-9404
Email: Hmaruyama@cardinals.com
700 Clark Ave, St. Louis, MO
Phone: (314) 345-9404
Email: Hmaruyama@cardinals.com
Owner
Attn: St. Louis Cardinals LLC
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
Billing
Attn: Hosei Maruyama
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hmaruyama@cardinals.com
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hmaruyama@cardinals.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Comb impact guides are rusted and need to be tested to insure roper impact calibration. | 2/18/2019 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 807.3 | No | No | Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect in 30 days. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Both handrails are cracked. | 7/12/2023 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Lower demarcation lights do not work. | 7/12/2023 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 802.6 | No | No | Replace two broken step demarcations. | 7/12/2023 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Demarcation light at the top landing does not work | 7/12/2023 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | Yes | No | Step/skirt clearances exceeded the allowed amount of .25. | 7/21/2023 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Right handrail is cracked and has possible pinching hazards. Replace handrail | 7/12/2023 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | No | No | Step/skirt clearances exceeded the allowed amount of .25 on the upper right side. | 8/13/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | Adjust right side skirt at top for proper clearence to pass the loaded gap and index testing | 8/13/2024 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Replace left side handrail | 8/26/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Adjust handrail tension- both handrails | 8/26/2025 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 806.2 | No | No | Provide lighting at upper end of unit per code. | 8/26/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4.1(b)(1) | No | No | On site maintenance records for call backs, repairs ,testing, & indexing to be on site and location of where they are located listed | 8/26/2025 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Clean out lower end pit of escalator - leaves and Debris | 8/26/2025 |