Inspection
Inspection Details
Equipment ID
21960
21960
Inspection Date
3/12/2026
3/12/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
bf719093-e4c1-4d52-a7ee-a1000211b9c8
bf719093-e4c1-4d52-a7ee-a1000211b9c8
Location
City View Apts-Bldg 30
110 N 17th St, Bldg 30, St. Louis, MO
Phone: (314) 588-1177
110 N 17th St, Bldg 30, St. Louis, MO
Phone: (314) 588-1177
Owner
Attn: Rock Rose City View SPE LLC DBA Gateway at City Park
c/o Blue Magma Residential, LLC
13095 Telecom Parkway N, Tampa, FL 33637
Phone: (813) 620-0800
c/o Blue Magma Residential, LLC
13095 Telecom Parkway N, Tampa, FL 33637
Phone: (813) 620-0800
Billing
Attn: Blue Magma Residential, Gateway at City Park Apartments
Blue Magma Residential, Gateway at City Park Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: lcapehart@bmresidential.com
Blue Magma Residential, Gateway at City Park Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: lcapehart@bmresidential.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | The machine room shall be kept clean. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The car top shall be kept clean. Clean the car top. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | Yes | Phase 2 fire service shall be operational. Elevator Red Tagged. | 1/28/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | No | Unable to test unintended movement. Unintended movement shall be tested in the down direction with 125% capacity, and in the up direction with an empty car. | 1/28/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | No | Unable to test unintended movement. Unintended movement shall be tested in the down direction with 125% capacity, and in the up direction with an empty car. | 1/18/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit floor shall be kept clean. Clean the pit. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The car top shall be kept clean. Clean the car top. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | No | The following violation remains from the category 5 test. Elevator company could not get weights on-site on 1/18/2023. Testing of unintended movement is scheduled for 3/31/23. Unable to test unintended movement. Unintended movement shall be tested in the down direction with 125% capacity, and in the up direction with an empty car. | 3/31/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | A two-way communication means between the car and a location staffed by authorized personnel shall be provided. Emergency phone rings, but on one answers. | 3/24/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | Yes | No | Not less than two lamps or sets of lamps of approximately equal illumination shall be provided. The cab lights are burnt out. | 3/24/2026 |