Inspection
Inspection Details
Equipment ID
11724
11724
Inspection Date
3/16/2026
3/16/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
05968be4-9781-4f95-bc76-e15d286603da
05968be4-9781-4f95-bc76-e15d286603da
Location
SSM-St. Louis University Hospital Legacy Building
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 257-1152
Email: patrick.schubert@ssmhealth.com
Owner
Attn: Brandy Kary
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
Billing
Attn: Robert Hicks Director, Plant Operations
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: Robert.Hicks@ssmhealth.com
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: Robert.Hicks@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Repair car door restrictor. | 8/12/2020 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | Car flooring is loose, protruding above car sill causing trip hazard. | 3/25/2026 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | x | Multiple hoist ropes do not meet minimum diameter requirements and had several breaks. Replace hoist ropes. Red tagged. | 7/16/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | Repair cab floor by entrance, it is a tripping hazard | 3/25/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Violation code 101.5b No ventilation in machine room, controllers are in extreme heat, over manufacturers recommendations | 3/25/2026 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated Missouri Operating Certificate in machine room | 3/25/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Elevator traction machine is leaking oil. Repair seals and gaskets | 3/25/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | 8th floor hoistway door interlock electrical cover is missing, replace cover. | 3/25/2026 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Need to test phase I & II fire service. Re-inspection required | 3/25/2026 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Phase II fire service operating instructions are missing inside elevator cab, need to install correct signage | 3/25/2026 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Hoistway door non vision panels (sight guards) are missing on the bottom and 3rd floor hoistway doors, needs repaired. | 3/25/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Elevator cab emergency lights do not work, needs repaired. Re-inspection required | 3/25/2026 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test elevator for operation on emergency power. Re-inspection required | 3/16/2026 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Machine room ventilation does not provide adequate heat (30 degrees in machine room) also, a large louve is wide open to outdoor air, needs repaired. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated Missouri Operating Certificate in machine room | |||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Phase II fire service operating instructions are missing inside elevator cab, need to install correct signage | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Hoistway door non vision panels (sight guards) are missing on the bottom and 3rd floor hoistway doors, needs repaired. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Elevator cab emergency lights do not work, needs repaired. Re-inspection required | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test elevator for operation on emergency power. Re-inspection required | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Elevator traction machine is leaking oil. Repair seals and gaskets | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | 8th floor hoistway door interlock electrical cover is missing, replace cover. |