Inspection
Inspection Details
Equipment ID
14166
14166
Inspection Date
12/19/2017
12/19/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
600 Washington Bldg
600 Washington Ave, St. Louis, MO
Phone: (314) 231-4940
600 Washington Ave, St. Louis, MO
Phone: (314) 231-4940
Owner
600 Tower LLC % Colliers International
600 Washington Ave, Ste 560, St. Louis, MO 63101
600 Washington Ave, Ste 560, St. Louis, MO 63101
Billing
Attn: 600 Tower LLC % Colliers International
600 Washington Ave, Ste 560, , MO 63101-1311
600 Washington Ave, Ste 560, , MO 63101-1311
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Doors closing automatically on Phase 2 | 11/28/2018 | |
conversion | conversion | n/a | Make appropriate repair in 2 ft. hole in wall of hatch and machine room | 2/28/2019 | ||
conversion | conversion | n/a | Terminal slowdown switch box cover missing. | 2/28/2019 | ||
conversion | conversion | n/a | Remove wiring from back wall of hoistway at 24th floor | 2/28/2019 | ||
MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | Replace deteriorating safety rod neoprene bushings on car sling. | 4/26/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace deteriorating safety rod neoprene bushings on car sling | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Replace missing restrictor angle on the 20th floor hoistway door | 1/19/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace damaged 4x4 electrical junction box on car top and provide cover | |||
A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.19.3 | x | Upon performing the required five year full load, the elevator safety governor was found to have an excessive amount of pull-through force. The maximum allowed pull-through force is 925 lbs. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. | 5/6/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room and hoistway inspection was performed, a full inspection shall be performed before the caregory 5 testing is completed. Reinspection is required. | 5/6/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test to complete Cat 5 test: test car safeties with rated load at rated speed, car buffer at rated speed with rated load, counterweight buffer at rated speed, machine brake with 125% of rated load, cab emergency lighting, alarm bell, 2 way communication, & test elevator for operation on emergency power. Re-inspection required | 5/20/2024 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | x | On phase 2 fire service, the car doors would not stay open. Elevator Red-tagged and removed from service. Re-inspection required | 5/20/2024 |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Unit appears to have emergency generator backup power, which needs to be tested to complete inspection. Re-inspection required |