Inspection
Inspection Details
Equipment ID
23903
23903
Inspection Date
1/28/2019
1/28/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26/26
26/26
External ID
a9db4687-88f9-42b3-b1fe-b0a48f482e94
a9db4687-88f9-42b3-b1fe-b0a48f482e94
Location
Fairfield Inn/ Residence
11920 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO
11920 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO
Owner
Midas Hospitality Group
1804 BORMAN CIRCLE DR, SAINT LOUIS, MO 63146-4161
1804 BORMAN CIRCLE DR, SAINT LOUIS, MO 63146-4161
Billing
Attn: Midas Hospitality Group
1804 BORMAN CIRCLE DR STE 100, SAINT LOUIS, MO 63146-4141
1804 BORMAN CIRCLE DR STE 100, SAINT LOUIS, MO 63146-4141
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 2/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Remove Water from pit | 11/1/2019 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Need maintenance control program on site posted on controller on or by next test | 12/21/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Need testing procedures in the MCP on or before 1/1/22 | 12/20/2021 |
| A17.1-2016 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Replace rusting conduit to Governor tail sheave switch 620.21 | 1/3/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | Channel pit floor to sump pump to drain standing water. 2.2.2.3 | 1/3/2023 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | Repair machine space lighting top of hoistway 2.7.6.3.2(c) | 1/3/2023 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | Hoisting belts have rouge all over need to be replaced | 10/19/2023 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.19.3 | Yes | No | Replace rusting pipe to govenor weight tail switch | 10/19/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | Replace rusting piping to governor weight tasil switch has not been corrected | 11/3/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Reinspection for rusted piping for tail shiv in pit, not corrected. Will have until Jan 15, 2024 to complete | 1/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | No | Repair switch push buttons in phase 2 fire service panel in car | 2/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | REMOVE WATER FORM THE PIT FLOOR | 11/6/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE SPACE | 11/6/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | Repair Switches in Phase 2 Fire Service Panel ( Call Cancel - Door open - Door Close ) Item 6.4 Section 2.27.3 | 2/19/2026 |