Inspection
Inspection Details
Equipment ID
14577
14577
Inspection Date
3/31/2026
3/31/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
David Tiemann
David Tiemann
Relief Valve Pressure
430
430
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14
14
External ID
d1008940-a2f4-4009-a260-58512fe3443f
d1008940-a2f4-4009-a260-58512fe3443f
Location
Boeing Bldg #106
6300 James S McDonnell Blvd, Berkeley, MO
Phone: (314) 234-6485
6300 James S McDonnell Blvd, Berkeley, MO
Phone: (314) 234-6485
Owner
Attn: Adam Goette
JLL @ Boeing
2600 N Hwy 94, St Charles, MO 63301
Phone: (557) 225-8939
Email: Adam.Goette@jll.com
JLL @ Boeing
2600 N Hwy 94, St Charles, MO 63301
Phone: (557) 225-8939
Email: Adam.Goette@jll.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell not working on emergency power | 7/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)5 | Yes | Yes | Gat switch not working red tagged out of service | 7/31/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Full load overspeed vlave test past due 90 day max on completing test | 8/23/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 12/15/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Machine room is missing GFCI. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Machine room walls have fire/smoke penetrations that shall be filled with appropriate fire caulking. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 3.29 | Yes | No | Disconnects and controller shall have car numbering. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | Yes | No | Machine room controller is missing appropriate alteration code plate. | 7/22/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit lighting shall be at least 10fc across pit floor. | 7/22/2025 |
| A17.1-2016 : Elevators | 5.14 - Supply Piping | 3.19.1 | Yes | No | Remove and properly cap previous oil line elbow fitting. | 7/22/2025 |