Inspection
Inspection Details
Equipment ID
26357
26357
Inspection Date
4/6/2026
4/6/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Aaron Bagley
Aaron Bagley
Relief Valve Pressure
387
387
Slide
NA
NA
Governor Rope Pull
Na
Na
Door Closing Force
14
14
External ID
81cad5b4-acf5-4860-8a47-bd9d4104dbc8
81cad5b4-acf5-4860-8a47-bd9d4104dbc8
Location
Meramac Elementary School
1340 W Outer 21 Rd, Arnold, MO
Phone: (314) 633-9677
Email: clayton.pezold@smwilson.com
1340 W Outer 21 Rd, Arnold, MO
Phone: (314) 633-9677
Email: clayton.pezold@smwilson.com
Owner
Attn: Clayton Pezold
Fox C-6 School District
745 Jeffco Blvd, Arnold, MO 63010
Phone: (314) 633-9677
Email: clayton.pezold@smwilson.com
Fox C-6 School District
745 Jeffco Blvd, Arnold, MO 63010
Phone: (314) 633-9677
Email: clayton.pezold@smwilson.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Acceptance test is incomplete. Need to test FAID. | 5/23/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 5/23/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. It dials out, but no answer. | 5/23/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | Pit electrical outlet missing cover. | 5/23/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Replace missing "Do not use elevator in case of fire" signage on multiple floors. | 5/23/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Disconnects shall be labeled with location of feeder breakers. | 5/23/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | 2.8.3.3 - Lobby fire alarm initiating devices shall not be within 3 feet of the HVAC vent. | 5/23/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | 2.8.3.3.4 - Pit fire alarm initiating devices shall not be below 48" from pit floor. Necessitates moving pit sprinkler to 24" above pit floor to maintain 24" heat to sprinkler relation. | 5/23/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | 2.8.3.3.2 - Sprinkler located at 2nd landing lobby shall have a FAID to shunt power before water flow (Machinery space when controller open). | 5/23/2024 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency lighting shall work with loss of main 120v power. | 5/23/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | 2.8.3.3.2 - Sprinkler located at 2nd landing lobby shall have a FAID to shunt power before water flow (Machinery space when controller open). | 6/26/2024 |