Inspection
Inspection Details
Equipment ID
14471
14471
Inspection Date
12/19/2017
12/19/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
F25/R24
F25/R24
External ID
Location
600 Washington Bldg
600 Washington Ave, St. Louis, MO
Phone: (314) 231-4940
600 Washington Ave, St. Louis, MO
Phone: (314) 231-4940
Owner
600 Tower LLC % Colliers International
600 Washington Ave, Ste 560, St. Louis, MO 63101
600 Washington Ave, Ste 560, St. Louis, MO 63101
Billing
Attn: 600 Tower LLC % Colliers International
600 Washington Ave, Ste 560, , MO 63101-1311
600 Washington Ave, Ste 560, , MO 63101-1311
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Floors 2-3-4 Fire phase 2 security cutout bypass not working when at floor | 2/4/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | No | Yes | Suspension rope displacement and damage after counter weight safety application. Replace ropes and counter weight safety slide. | 2/22/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace drive sheave groove liners. | 4/26/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 5/28/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: There is no fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car, as required. | 1/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | The hoistway door pick up roller on the 24th floor is deteriorated and shall be replaced. | 1/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Visual conformation of fire service inoperable. Repair or replace. | 1/20/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator equipped with back up generator. Perform emergency power testing. | 1/20/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator shall be tested for operation on emergency power. Re-inspection required | 6/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Visual conformation of fire service inoperable. Repair or replace. | 6/5/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator shall be tested for operation on emergency power. Re-inspection required |