Inspection
Inspection Details
Equipment ID
7166
7166
Inspection Date
1/29/2019
1/29/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
David Scott
David Scott
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
28b1aaac-c3c4-484b-93ce-24df492b8d6f
28b1aaac-c3c4-484b-93ce-24df492b8d6f
Location
Lindbergh High School
4900 S LINDBERGH BLVD, SAINT LOUIS, MO
4900 S LINDBERGH BLVD, SAINT LOUIS, MO
Owner
Lindbergh School District
4900 S LINDBERGH BLVD, SAINT LOUIS, MO 63126-3235
4900 S LINDBERGH BLVD, SAINT LOUIS, MO 63126-3235
Billing
Attn: Lindbergh School District
9350 SAPPINGTON RD, SAINT LOUIS, MO 63126-3043
9350 SAPPINGTON RD, SAINT LOUIS, MO 63126-3043
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line is not working. Re-inspection required | 1/25/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | Yes | Yes | Emergency phone is not working. Red-tagged, Re-inspection required | 2/8/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Lighting in cab and on cartop is not working. Power is temporarily disconnected | 1/21/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Lights in the pit shall work. Power temporarily disconnected | 1/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired. Have serviced or replaced | 1/21/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room doors shall be self locking, replace missing lock mechanism | 1/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | Yes | Emergencyy alarm & light do not work. Red-tagged, Re-inspection required | 2/8/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working, appears to have no live phone line. Re-inspection required | 2/8/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Repair holes in machine room ceiling and fire caulk around copper pipe and sprinkler pipe penetrations thru walls in machine room to preserve fire rating. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Elevator has sprinkler head in machine room. Install heat detector within 2 feet of head and shunt trip disconnect system to remove power from elevator equipment in event sprinkler head releases water. Re-inspection required |