Inspection
Inspection Details
Equipment ID
13419
13419
Inspection Date
1/31/2019
1/31/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
21b6d74d-bc6b-4fe7-ad47-a26bfbac5c7f
21b6d74d-bc6b-4fe7-ad47-a26bfbac5c7f
Location
10th & Lami
1000 LAMI ST, SAINT LOUIS, MO
1000 LAMI ST, SAINT LOUIS, MO
Owner
10th& Lami Inc
1000 LAMI ST, SAINT LOUIS, MO 63104-4259
1000 LAMI ST, SAINT LOUIS, MO 63104-4259
Billing
Attn: Interfaith Residence
4385 MARYLAND AVE, SAINT LOUIS, MO 63108-2703
4385 MARYLAND AVE, SAINT LOUIS, MO 63108-2703
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Fire service key switch bezels not readable in car and hallway | 2/19/2019 | ||
conversion | conversion | conversion - reinspect | Emergency phone not working | 1/31/2019 | ||
conversion | conversion | n/a | Clean pit of debris | 2/19/2019 | ||
conversion | conversion | n/a | Repair or replace electric eyes | 2/19/2019 | ||
conversion | conversion | n/a | Do not use machine room as storage space | 2/19/2019 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current operating certificate in machine room. | 2/19/2019 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Light rays are not working, mechanical edge works. Repair/replace light rays. Re-inspection required | 11/24/2022 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone is not working, needs repaired. Re-inspection required | 1/23/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Re-inspection to check door re-opening device (light ray), still not working, needs repaired. Re-inspection required | 1/23/2024 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Elevator cab phone is still not working. Re-inspection required | 1/23/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Door reopening device (light ray) does not work, needs repaired. Re-inspection required | 5/7/2024 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work. Re-inspection required | 5/7/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Car failed 15 minute stand test, tech determined leaking back through the valve. Repair or replace as needed. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Provide means to collect oil scavenged, return line into tank to be removed.(due to extreme depth of pit, place bucket in machine room) |