Inspection
Inspection Details
Equipment ID
5123
5123
Inspection Date
4/20/2026
4/20/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
520
520
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
c479fb43-c37c-44a1-899a-bbd8f1335eab
c479fb43-c37c-44a1-899a-bbd8f1335eab
Location
Alexian Court Apartments
2636 Chippewa St, St. Louis, MO
Phone: (314) 771-5604
2636 Chippewa St, St. Louis, MO
Phone: (314) 771-5604
Owner
Attn: Kari Welker
Alexian Court Apartments
2636 Chippewa St, St. Louis, MO 63118
Phone: (314) 771-5604
Alt Phone: (618) 537-6112 Ext: 1000
Email: kwelker@thecapitalrealty.com
Alexian Court Apartments
2636 Chippewa St, St. Louis, MO 63118
Phone: (314) 771-5604
Alt Phone: (618) 537-6112 Ext: 1000
Email: kwelker@thecapitalrealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency light and bell not working | 8/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need a maintenance control program on site posted on controller asap | 11/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone shall be operational and code compliant. The answering service can not be heard. | 12/29/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from the pit floor. The pit shall be kept clean and dry. | 12/4/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove fire panels on the wall in the machine room. Machine room shall only have equipment related to the operation of the elevator. | 6/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 6/5/2023 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | Yes | No | Packing on jack is leaking. Take corrective action as needed. | 5/8/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Fire panels on wall in machine room. Only elevator related equipment is allowed. | 6/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 6/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. | 4/20/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Fire panels located on the wall in the machine room. Only elevator related equipment allowed. Cited multiple years. | 4/20/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Outlet in machine room needs to have a cover installed. | 4/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/20/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing shall be documented monthly. | 4/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No MO State operating certificate in the machine room. |