Inspection
Inspection Details
Equipment ID
16257
16257
Inspection Date
4/29/2026
4/29/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Jerry Christian
Jerry Christian
Relief Valve Pressure
Slide
00
00
Governor Rope Pull
00
00
Door Closing Force
18
18
External ID
a517df81-887d-4099-8785-484492df3354
a517df81-887d-4099-8785-484492df3354
Location
Lofts at 415
415 N 3rd St, St. Joseph, MO
Phone: (816) 749-4663
415 N 3rd St, St. Joseph, MO
Phone: (816) 749-4663
Owner
Attn: CAA 3 LLC
CAA 3 LLC
3432 E Russell St, Nesa, AZ 85213
Phone: (000) 000-0000
CAA 3 LLC
3432 E Russell St, Nesa, AZ 85213
Phone: (000) 000-0000
Billing
Attn: Ashley Casella
Mitchell Park Plaza
1300 S 11th St, Ste 100, St. Joseph, MO 64503
Phone: (816) 749-4663
Email: ashley@epic-pm.com
Mitchell Park Plaza
1300 S 11th St, Ste 100, St. Joseph, MO 64503
Phone: (816) 749-4663
Email: ashley@epic-pm.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Provide tye ABC fire extinguisher inside control room near access door | 7/29/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 7/26/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | 8/24/2021 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Replace broken bezel identification marking for firefighter keyswitch | 8/24/2021 |
| A17.1-1996 : Elevators | 3.26 - Broken rope, chain, or tape switch | 1001.2(c)(9) | Yes | No | Slack belt switch does not function. | 8/13/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | 8/24/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace missing car direction lantern fixture in car enclosure opening. | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No MCP | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(5) | No | No | Written procedures for tests and inspections need to be kept in the control room. | 9/12/2024 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.19.2 | Yes | Yes | Perform annual no load safety test | 8/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 9/12/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 9/12/2024 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace missing car direction lantern fixture in the car enclosure | 9/12/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit access door needs to be self-locking | 9/12/2024 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | No | No | Install heat detector within 24 inches from each machine room sprinkler | 9/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 8/22/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions next to hall firefighter keyswitch | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(5) | No | No | Keep written procedures for tests and inspections on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Perform unintended motion and ascending car protection tests | 8/22/2023 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Perform full load safety test | 8/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in the control space. | 9/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 7/2/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | DOOR CLOSE BUTTON IS LABELED #1 | 9/12/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.1a | No | No | HOLE IN MACHINE ROOM CELING NEEDS TO BE PATCHED AND FIRE RATED | 9/12/2024 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | CAR DOOR GAP IS >1/2" . NEEDS TO BE ADJUSTED | 9/12/2024 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.6 | No | No | DOOR GAP IS >1/2'' | 6/27/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | SUPPLY WORKING LIGHT AND BELL | 4/29/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE WORKING PHONE |