Inspection
Inspection Details
Equipment ID
12090
12090
Inspection Date
4/28/2026
4/28/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
530e1ca3-ada6-4501-b4d6-8eb7acadde89
530e1ca3-ada6-4501-b4d6-8eb7acadde89
Location
Marriott St Louis Grand
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
Alt Phone: (314) 418-5838
Email: valery.reisig@marriott.com
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
Alt Phone: (314) 418-5838
Email: valery.reisig@marriott.com
Owner
Attn: Marriott St. Louis Grand
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: Brad.Mandrell@marriott.com
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: Brad.Mandrell@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Repair emergency lights in car. | 11/5/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light not working. | 12/11/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Repair pit light. | 11/5/2025 |
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 1001.2(c)(28) | No | No | Replace anti-rotation devices on counterweights. | 11/5/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light (still) inoperative. | 3/10/2021 |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1001.2(b)(15) | Yes | Yes | Car lowered, stopped and held 125% capacity, however adjustment needs to be made for brake pick gaps to a consistent .005 as per brake data tag. Reinspection only. | 3/28/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 3/28/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the elevator machine room | 11/5/2025 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | Repair or replace travel cable due to damage and/or breakage of cable insulation at basement floor loop | 11/5/2025 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop | 11/5/2025 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop | 3/11/2026 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | Yes | No | Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop | 4/22/2026 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | No | No | There shall be permanent means of temperature control inside of the elevator machine room. | 4/28/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Unit failed to perform firefighters operation and is red tagged at this time. | 4/28/2026 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | No | No | There shall be permanent means of temperature control inside of the elevator machine room. |