Inspection
Inspection Details
Equipment ID
7712
7712
Inspection Date
4/29/2026
4/29/2026
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
620
620
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
0b4af79d-380a-45c8-a2ba-60d981368a9d
0b4af79d-380a-45c8-a2ba-60d981368a9d
Location
3401 Technology Drive LLC
3401 Technology Dr, Lake St. Louis, MO
Phone: (314) 744-8994
3401 Technology Dr, Lake St. Louis, MO
Phone: (314) 744-8994
Owner
Attn: C/O Infinity & Beyond Property Management
3401 Technology Drive LLC
8 the Pines Unit D, Chesterfield, MO 63141
Phone: (636) 728-5126
Email: valerie.rizzello@svn.com
3401 Technology Drive LLC
8 the Pines Unit D, Chesterfield, MO 63141
Phone: (636) 728-5126
Email: valerie.rizzello@svn.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV not sealed or tagged. Perform OSV test on or before next annual inspection. | 6/3/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 9/6/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide existing battery backup lowering unit to work correctly. | 2/29/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide existing battery backup lowering unit to work. | 4/19/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP. | 5/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related items from the elevator machine room.(janitorial supplies and equipment) | 5/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide existing elevator machine room lights to work. | 5/15/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/15/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide existing lights in machine room to work | 5/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related items for the machine room, janitorial supplies & equipment | 5/15/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 6/3/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Cylinder packing(s) are worn and leaking, repair as needed. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Provide means for phone operator to identify location. | 4/29/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Testing of OSV must be performed to complete inspection. Re-inspection required | 7/27/2026 |