Inspection
Inspection Details
Equipment ID
8675
8675
Inspection Date
5/5/2026
5/5/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
440
440
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
2185891c-46ad-4491-8225-f0614b48295b
2185891c-46ad-4491-8225-f0614b48295b
Location
Cambridge Court Condos
910 Claytonbrook Dr, Ballwin, MO
Phone: (636) 227-0012
910 Claytonbrook Dr, Ballwin, MO
Phone: (636) 227-0012
Owner
Attn: Kathleen Peick
Cambridge Court Condos c/o Community Property Management
242 Old Sulphur Springs Rd, Manchester, MO 63021
Phone: (636) 227-8688
Email: kathleen@cpmgateway.com
Cambridge Court Condos c/o Community Property Management
242 Old Sulphur Springs Rd, Manchester, MO 63021
Phone: (636) 227-8688
Email: kathleen@cpmgateway.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency lighting shall be operational. | 9/2/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate in the machine room. | 10/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Per the MO AHJ, this elevator has been confirmed to have a single bottom jack. The jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. | 9/5/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | 8/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 8/6/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 8/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. Note: Last updated 7/2022. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing and self-locking. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. Note: Last updated 7/2022 | 5/5/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing and self-locking. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 5/5/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | This elevator is equipped with an overspeed valve. A category 5 test shall be perfomred on the overspeed valve, last tested in 2013. To be tested immediately. | 5/5/2026 |