Inspection
Inspection Details
Equipment ID
14890
14890
Inspection Date
1/22/2019
1/22/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
184bc19f-6fa4-43fe-aa41-fdc172472d42
184bc19f-6fa4-43fe-aa41-fdc172472d42
Location
City View Apts-Bldg 30
110 N 17TH ST BLDG 30, SAINT LOUIS, MO
110 N 17TH ST BLDG 30, SAINT LOUIS, MO
Owner
Attn: Mills Properties Inc Cityview Apartments
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | 2.18.5.3 - A governor rope data tag shall be installed. | 5/27/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | 2.20.2.2 - A suspension rope data tag shall be installed. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | x | 2.11.11.4 - The GAL type A hall door hanger safety retainers shall be installed according to manufacturers specifications. | 9/15/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | x | The hoist ropes are bad and shall be replaced ASAP. Other unit in building was red tagged. Allowing 60 days to replace ropes since other unit is red tagged. | 6/11/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | Unable to complete the category 5 portion of the test. A category 5 test shall be completed. Category 1 items were completed. | 6/11/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.18.7 | Hoist ropes shall have data tags installed. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | x | Call cancel button on fire service is not working. | 8/27/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone is not working. | 8/27/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | x | Call cancel button on fire service is not working. (Violation not checked during phone re-inspect on 8/27/24) | 2/20/2025 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door lock is broken and must be repaired to prevent access to machine room by unauthorized persons. Access doors shall be self-closing and self-locking. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | A permanent and unobstructed means of access shall be provided to machine room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Phase II fire service, call cancel button not functioning. (2nd Notice) |