Inspection
Inspection Details
Equipment ID
8676
8676
Inspection Date
5/13/2026
5/13/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Ronald Hogue, Jr
Ronald Hogue, Jr
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
eb684e4f-cdad-45c2-9b53-9a4e91ed398a
eb684e4f-cdad-45c2-9b53-9a4e91ed398a
Location
Cambridge Court Condos
912 Claytonbrook Dr, Ballwin, MO
Phone: (636) 227-0012
912 Claytonbrook Dr, Ballwin, MO
Phone: (636) 227-0012
Owner
Attn: Kathleen Peick
Cambridge Court Condos c/o Community Property Management
242 Old Sulphur Springs Rd, Manchester, MO 63021
Phone: (636) 227-8688
Email: kathleen@cpmgateway.com
Cambridge Court Condos c/o Community Property Management
242 Old Sulphur Springs Rd, Manchester, MO 63021
Phone: (636) 227-8688
Email: kathleen@cpmgateway.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | The existing sump pump in the pit shall be operational. | 3/22/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove fluids from the pit. The pit shall be kept clean and dry. | 3/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is expired and shall be serviced or replaced. | 3/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Per the MO AHJ, this elevator has been confirmed to have a single bottom jack. The jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. If the jack is replaced, documentation shall be available on-site at all time and shall be provided to the state. | 9/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 8/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 12/4/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing and self-locking. | 12/4/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Pit light shall work. | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. Note: last updated 7/2022 | 12/11/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing and self-locking. | 12/11/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Pit light shall work. | 12/11/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve, last tested in 2013. | 12/11/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. Note: last updated 7/2022 | 5/13/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing and self-locking. | 5/13/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Pit light shall work. | 5/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve, last tested in 2013. | 5/13/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. Note: last updated 7/2022 |