Inspection
Inspection Details
Equipment ID
1981
1981
Inspection Date
4/22/2026
4/22/2026
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Jared Gansen
Jared Gansen
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
f=16/r=18
f=16/r=18
External ID
cf733746-f9d6-467d-8467-b2ecf10f2996
cf733746-f9d6-467d-8467-b2ecf10f2996
Location
3M Company
2120 E Austin Blvd, Nevada, MO
Phone: (417) 667-7851
2120 E Austin Blvd, Nevada, MO
Phone: (417) 667-7851
Owner
Attn: Jordan Woods
3M Company
PO Box 33121, St. Paul, MN 55133
Phone: (417) 283-0366
Alt Phone: (816) 729-8533
Email: jordan.woods1@cbre.com
3M Company
PO Box 33121, St. Paul, MN 55133
Phone: (417) 283-0366
Alt Phone: (816) 729-8533
Email: jordan.woods1@cbre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Both front and rear gate reopening devises need replaced | 2/7/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Must make Emergency light operable. 1.5 | 1/9/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emergency alarm operable. 1.6 | 1/9/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Elevator pit must be kept free of Debris. 8.6.4.7 | 1/24/2023 |
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Rear Gate Re-opening devise must be made operable. 1001.2(a)(1) | 1/24/2023 |
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Must repair or replace Protective Boot for gate re-opening device front gate. 1001.2(a)(1). (cuts tears and missing section) | 1/24/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Must make Phase II fire service operable. 211.7 ( doors operate properly but car will not leave primary floor) | 1/24/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Alarm Operable. 8.6.4.15 | 4/22/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Must make Phase II Fire Service Key Switch Operable. 6.4 | 4/22/2026 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must perform Cat 5 OSV (over speed valve)test/insp. | 4/22/2026 |
| A17.1-2016 : Elevators | 1.1 - Door Reopening Device | 8.11.2.1.1(a) | No | No | Must make Car Gate Reopening devise operable. 1.18 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency alarm bell operable. 1.6 |