Inspection
Inspection Details
Equipment ID
11779
11779
Inspection Date
5/15/2026
5/15/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Michael Bales
Michael Bales
Relief Valve Pressure
n/a
n/a
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
676fd459-ea90-45c4-8b51-723b28bda709
676fd459-ea90-45c4-8b51-723b28bda709
Location
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO
Phone: (660) 236-6107
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
200 N Banquet Dr, Marshall, MO
Phone: (660) 236-6107
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Owner
Attn: Con Agra Frozen Foods
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)10 | No | No | No easy access to pit | 8/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency phone not working | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 8/12/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit full of trash. Pieces of broken pallets. | 8/1/2022 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | missing capacity plate in car | 5/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | repair pit stop switch | 5/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | lots of broken pallet debris on pit floor clean same | 5/15/2026 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | stop sw in cab knocked inside of car station. remount and test | 5/15/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Provide capacity plate in car. | 6/1/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | Yes | Yes | Pit switch broken. | 6/1/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | Yes | Debris in pit, remove. | 6/1/2026 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | Yes | In car stop switch broken. | 6/1/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | Yes | Yes | Both landing door guides and related devices aged and badly worn. Repair as necessary. | 6/1/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Yes | Yes | Hoistway landing door vision panels damaged/missing. | 6/1/2026 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | Yes | Yes | Guide shoe liner missing, causing severe damage to shoe frame. | 6/1/2026 |
| MO Minimum : Elevators | (N) - Guide Rails | (N)2 | Yes | Yes | Guide rail SEVERELY worn from missing guide shoe. Unit removed from service. | 6/1/2026 |