Inspection
Inspection Details
Equipment ID
3263
3263
Inspection Date
2/13/2019
2/13/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Bales
Michael Bales
Relief Valve Pressure
290
290
Slide
Governor Rope Pull
Door Closing Force
13
13
External ID
ebbfadb8-221d-4795-b670-d5e47f1d3e4e
ebbfadb8-221d-4795-b670-d5e47f1d3e4e
Location
Powell Gardens
1609 NW US HIGHWAY 50, KINGSVILLE, MO
1609 NW US HIGHWAY 50, KINGSVILLE, MO
Owner
Powell Gardens
1609 NW US HIGHWAY 50, KINGSVILLE, MO 64061-9130
1609 NW US HIGHWAY 50, KINGSVILLE, MO 64061-9130
Billing
Attn: Powell Gardens
1609 NW US HIGHWAY 50, KINGSVILLE, MO 64061-9130
1609 NW US HIGHWAY 50, KINGSVILLE, MO 64061-9130
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | required to have minium of 2 working lights in the elevator cab, at the time of the inspection only one light was working | 7/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, phone line was dead | 8/21/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | the fire service initiating devices have all been removed, the smoke detectors all failed because it is a high dust environments | 2/23/2022 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.11.3.1.5(c) | No | No | water in the jack head from the last time that the pit flooded needs to be cleaned out. | 3/27/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | monthly fire service test log is not being filled out monthly | 3/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log needs to be filled out monthly | 3/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag is from 2020, needs to be inspected annually. | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | fire service initiating devices have all been removed, fire alarm control panel has been turned off, outside elevator smoke detectors won't work, need to use alternate initiating devices to recall the elevator, high dust environment | 6/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, phone line dead, no dial tone, provide working phone line | 6/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean the pit, water and oil mixture couple of inched deep | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Elevator pit is full of water mixed with oil, water is on the head of the jack, drain the pit, provide means to prevent the accumulation of groundwater in the pit | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | The monthly fire service test log is not being filled out, post a monthly fire service test log in the machine room and fill it out log monthly | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Machine room space heater cannot be hooked to the line side of the main line disconnect for the elevator, must have separate power for machine room space heater | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Junction box in the machine room has bare wires hanging out of it, cap exposed wires and install cover on junction box | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | All fire service initiating devices have been removed, fire alarm control panel has been disabled, repair system or apply for variance from state of Missouri | 4/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lights did not come on, alarm bell worked | 4/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not have an active phone line, provide working phone line | 4/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Elevator pit is full of water mixed with oil, water is on the head of the jack, drain the pit, provide means to prevent the accumulation of groundwater in the pit | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | The monthly fire service test log is not being filled out, post a monthly fire service test log in the machine room and fill it out log monthly | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Machine room space heater cannot be hooked to the line side of the main line disconnect for the elevator, must have separate power for machine room space heater | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Junction box in the machine room has bare wires hanging out of it, cap exposed wires and install cover on junction box | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | All fire service initiating devices have been removed, fire alarm control panel has been disabled, repair system or apply for variance from state of Missouri | 7/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lights did not come on, alarm bell worked, replace emergency battery | 7/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not have an active phone line, provide working phone line | 7/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) | Yes | No | repair main landing hall button station, fire service indicator jewel is pushed into faceplate | 7/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine room fire extinguisher is missing, provide fire extinguisher in the machine room | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | All fire service initiating devices have been removed, fire alarm control panel has been disabled, repair system or apply for variance from state of Missouri | 3/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the state certificate is to be posted in the machine room | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | All fire service initiating devices have been removed, fire alarm control panel has been disabled, repair system | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | No "in case of fire use stairs sign", needed on bottom landing |