Inspection
Inspection Details
Equipment ID
58
58
Inspection Date
1/31/2019
1/31/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Christopher Bolin
Christopher Bolin
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
20
20
External ID
420ce3a3-3473-419c-9c1d-2a84134bb648
420ce3a3-3473-419c-9c1d-2a84134bb648
Location
Colony Plaza
404 SAINT LOUIS AVE, EXCELSIOR SPRINGS, MO
404 SAINT LOUIS AVE, EXCELSIOR SPRINGS, MO
Owner
Colony Plaza LP
40 COURT ST STE 650, BOSTON, MA 00000
40 COURT ST STE 650, BOSTON, MA 00000
Billing
Attn: Colony Plaza
404 SAINT LOUIS AVE, EXCELSIOR SPRINGS, MO 64024-2174
404 SAINT LOUIS AVE, EXCELSIOR SPRINGS, MO 64024-2174
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Perform monthly fire service test and post a log in the machine room | 3/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone speaker was barely audible, could not hear the operator at all | 3/17/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | the alarm bell did not work on normal power | 5/25/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | monthly fire service test log has not been filled out since June 2021 | 5/25/2022 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | emergency light battery is dead, replace battery | 5/25/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | monthly fire service test log in the machine room was last filled out on December 2021, could not find a 2022 or 2023 fire service test log in the machine room | 3/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | clean up oil on the car top, it is starting to leak into the cab | 3/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 2.8.1 | Yes | No | traveling cable jacket is worn through, bare wires exposed, replace traveling cable | 6/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit | 3/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | New power cable ran through the block wall in the machine room needs to be Fire caulked and flex needs to be secured to the wall. | 3/12/2026 |