Inspection
Inspection Details
Equipment ID
22797
22797
Inspection Date
5/21/2026
5/21/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
520
520
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
a169487f-d5be-4419-aeb0-48cb82fb22fb
a169487f-d5be-4419-aeb0-48cb82fb22fb
Location
Whole Foods
4577 West Pine Blvd, St. Louis, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
4577 West Pine Blvd, St. Louis, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
Owner
Attn: Whole Foods
Whole Foods
4577 West Pine, St. Louis, MO 63108
Phone: (417) 246-5510
Alt Phone: (417) 379-4704
Whole Foods
4577 West Pine, St. Louis, MO 63108
Phone: (417) 246-5510
Alt Phone: (417) 379-4704
Billing
Attn: Certificate Management
Whole Foods c/o ATIS
600 Emerson Rd Ste 225, St. Louis, MO 63141
Phone: (314) 668-7361
Alt Phone: (417) 379-4704
Email: wholefoods@atis.com
Whole Foods c/o ATIS
600 Emerson Rd Ste 225, St. Louis, MO 63141
Phone: (314) 668-7361
Alt Phone: (417) 379-4704
Email: wholefoods@atis.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative cab hands free phone. | 7/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post operating certificate inside elevator equipment room. | 10/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | No | No | Provide self locking lock on machine room door. | 10/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Initiating device (heat detector) disconnected inside elevator equipment room. Did NOT red tag. | 7/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 10/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 8.7.2.14 | No | No | Cab walls pushed off their fasteners. Secure all loose, broken, cab to platform connections. | 10/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Install correct keyed lock cylinder on the firefighter's cab swing door. Did NOT red tag. | 7/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Oil minder has shut sump pump off. Pit has water and oil in it. | 10/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering device is not working, needs repair. Re-inspection required | 6/22/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri operating certificate in machine room | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering device is not working | 5/8/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 9/15/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 9/15/2025 |