Inspection
Inspection Details
Equipment ID
20789
20789
Inspection Date
5/27/2026
5/27/2026
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
1"
1"
Governor Rope Pull
40/200
40/200
Door Closing Force
23/22
23/22
External ID
67c1ce92-24b1-488d-9447-3e31945560ac
67c1ce92-24b1-488d-9447-3e31945560ac
Location
St. Louis University High School
4970 Oakland Ave, St. Louis, MO
Phone: (314) 531-0330
Email: rfigge@sluh.org
4970 Oakland Ave, St. Louis, MO
Phone: (314) 531-0330
Email: rfigge@sluh.org
Owner
Attn: St. Louis University High School
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: mfischer@sluh.org
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: mfischer@sluh.org
Billing
Attn: St. Louis University High School
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: jrankin@sluh.org
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: jrankin@sluh.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Make emergency light operational. | 7/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/29/2019 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.2.1(a) | No | No | Wiring prints and maintenance logs shall be kept on-site. | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.11.2.1.2(l) | No | No | Up-to-date wiring diagrams shall be provided on-site. | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency lowering device shall be operational. | 6/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | No wiring diagram in the machine room. | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. No Answer. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 2.12.7 | Yes | No | Hoistway Door Safety Retainers/Fire tabs shall be installed at the bottom of all hoistway doors. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State Operating Permit shall be obtained and displayed in the Equipment Room. (EXPIRED: 6/21/2020) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service must be tested and properly documented monthly on Log Sheet. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Up-to-date wiring diagrams shall be provided on-site | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Suspension Rope Guards on hoist machine are missing Reinstall and adjust for proper clearance. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | No | No | Replace missing Phase 1 instruction signage at Recall Floor. |