Inspection
Inspection Details
Equipment ID
8919
8919
Inspection Date
5/26/2026
5/26/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Tommy Hogge
Tommy Hogge
Mechanic Name
Joseph Ottoline
Joseph Ottoline
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
e898cb74-c500-4acf-9dc9-3fad8f3f173b
e898cb74-c500-4acf-9dc9-3fad8f3f173b
Location
Weinberg Bldg
8348 Delcrest Dr, St. Louis, MO
Phone: (314) 991-2055
8348 Delcrest Dr, St. Louis, MO
Phone: (314) 991-2055
Owner
Attn: Crown Center
Council Apartments II
8350 Delcrest Dr, St. Louis, MO 63124
Phone: (000) 000-0000
Email: tvohsen@crowncenterstl.org
Council Apartments II
8350 Delcrest Dr, St. Louis, MO 63124
Phone: (000) 000-0000
Email: tvohsen@crowncenterstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.19 Gears, Bearings, and Flexible Couplings | 8.11.2.1.2(v) | No | No | A grease seal on the drive machine is leaking excessively and shall be replaced. | 7/5/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 6/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 6/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required. | 6/21/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 7/5/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be clean of debris | 6/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | A grease seal on the drive machine is leaking and needs to be replaced | 2/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | No documentation for procedures and tests | 2/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is out. Re-inspection required | 1/10/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Hoist ropes are showing signs of wear and rouge. Two hoist ropes are at maximum stretch. Red-tagged elevator until hoist ropes are replaced and re-inspected. | 1/10/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned of debris | 2/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is out. Re-inspection required | 2/2/2024 |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | Yes | No | Equip elevator with platform guard no less than 48 “ long. | 5/26/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | Test all smoke and heat detectors connected to elevator controller. Smoke detectors, when activated shall recall elevator to primary or alternate landing. Also test phase 1 and 2 fire service key operation. | 5/26/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Test elevator for operation on emergency power. | 5/26/2026 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Provide working hvac system in elevator machine room to keep temperature within elevator equipment operating range. | 5/26/2026 |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 2.18.5 | Yes | No | Provide governor rope data tag on governor rope. | 5/26/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Provide sump pump in elevator pit. | 5/26/2026 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | Provide alteration code data plate in machine room permanently marked. | 5/26/2026 |
| A17.1-2016 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4 | Yes | No | Test counterweight seismic device. | 5/26/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Fire service will not reset from fire service to normal operation. | 5/27/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Need to perform generator test. Re-inspection required | 5/27/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Unable to complete smoke detector test due to fire service reset not working properly, need to perform smoke test. Re-inspection required | 5/27/2026 |