Inspection
Inspection Details
Equipment ID
7155
7155
Inspection Date
12/22/2017
12/22/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
HoteLumiere
901 North 1st St, St. Louis, MO
Phone: (314) 881-7777
901 North 1st St, St. Louis, MO
Phone: (314) 881-7777
Owner
Pinnacle Entertainment
3800 Howard Huges Parkway, Las Vegas, NV 89109
3800 Howard Huges Parkway, Las Vegas, NV 89109
Billing
Attn: HoteLumiere
901 North 1st St, , MO 63102
901 North 1st St, , MO 63102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean oil and rags off car top | 2/26/2024 |
| conversion | conversion | n/a | No | No | Machine room lights out toward the back - repair. | 2/26/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need repair. 10 ft candle minimum | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean oil and rags off cartop. | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 12/12/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean oil off of floor and machine. | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency phone shall work. | 8/5/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need repair. 10 ft candle minimum | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door needs to be self closing and locking | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate in the machine room | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. REINSPECT REQUIRED | 3/29/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Suspension ropes are undersized with rouge. RED TAGGED | 3/29/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Car does not recall on fire service phase 1. RED TAGGED | 3/29/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need to be 10 ft candles minimum | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door needs to be self locking & self closing | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in the elevator machine room | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing | 1/23/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current Missouri Operating Certificate needs to be displayed in machine room | 1/23/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 1/23/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work | 1/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door restrictor is missing parts. Replace same | 6/11/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program needs to be updated | 1/23/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working | 6/11/2025 |
| A17.1-2016 : Elevators | 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators | 2.27.3 | Yes | Yes | Ph1 Audible signal shall not be active when the car is at the recall level. | 11/26/2025 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 2.17.3 | Yes | Yes | Car safety slide shall be between 4"-22" | 11/26/2025 |