Inspection
Inspection Details
Equipment ID
26826
26826
Inspection Date
6/2/2026
6/2/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
NA
NA
Slide
Softset
Softset
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
d31c720a-54c7-40bf-ae43-5853300ae33f
d31c720a-54c7-40bf-ae43-5853300ae33f
Location
St. Charles Community College RWIC
2400 Interstate Dr, Wentzville, MO
Phone: (000) 000-0000
2400 Interstate Dr, Wentzville, MO
Phone: (000) 000-0000
Owner
Attn: St. Charles Community College
St. Charles Community College
4601 Mid Rivers Mall Dr, St Peters, MO 63376
Phone: (636) 922-8493
Email: chazel@stchas.edu
St. Charles Community College
4601 Mid Rivers Mall Dr, St Peters, MO 63376
Phone: (636) 922-8493
Email: chazel@stchas.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine room door shall be self-closing and self-locking. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine room door shall have smoke seal around the door. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.1.3 | Yes | No | Relocate duct smoke detector reset switch to outside machine room. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Fill smoke/fire penetrations with approved fire caulk. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Mainline and lighting disconnects need labeling for purpose of each. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | n/a | Yes | No | NEC 110.26 - Machine room lighting disconnect does not meet 30" rule/not co-planer. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 2.26 | Yes | No | Machine room lighting disconnect has a fused neutral. | 6/30/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Fire caulk/fill holes and voids in hoistway walls. | 6/30/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Hoistway sills shall be flush with flooring, currently > 1" gap b/w sill and flooring. | 6/30/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.4 | Yes | No | Pit sump pump controller shall be relocated to outside the pit. | 6/30/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | Yes | No | Phase 1 fire hat does not work. | 6/30/2025 |