Inspection
Inspection Details
Equipment ID
14612
14612
Inspection Date
6/8/2026
6/8/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
350
350
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
22
22
External ID
280653b0-ae66-4d6b-8d93-3765332eed49
280653b0-ae66-4d6b-8d93-3765332eed49
Location
Metro Lofts
4535 Forest Park Ave, St. Louis, MO
Phone: (314) 367-2400
4535 Forest Park Ave, St. Louis, MO
Phone: (314) 367-2400
Owner
Attn: Metro Lofts LLC
Metro Lofts LLC
4535 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 367-2400
Email: metroflatsmanager@millsproperties.com
Metro Lofts LLC
4535 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 367-2400
Email: metroflatsmanager@millsproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 12/3/2018 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed and must have a cat 5 weight test performed within 90 days or less | 3/30/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. | 1/11/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4”. The anchor bolts shall be cut off smooth on the cart top as not to cause a tripping hazard or potential injury to maintenance and emergency personnel. | 6/8/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 6/8/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The phone in the elevator cab is not working. Re-inspection required | 9/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | This unit has had a drop ceiling installed and the bolts are sticking through the car top, the bolts need to be cut off so that they don't cause a tripping hazard for the maintenance personnel working on the cartop | 6/8/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 6/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | 6/8/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working. Check & repair this phone for proper operation and passenger safety. Re-inspection required | 6/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4". The anchor bolts shall be cut off smooth on the car top as not to cause a tripping hazard or potential injury to maintenance or emergency personnel. This is the second notice about the anchor bolts, needs to be completed within 30 days. Re-inspection required | 6/8/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current copy of the state certificate shall be displayed in the machine room | 6/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working. Check & repair this phone for proper operation and passenger safety. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The evaporator for the air conditioning unit in the machine room is leaking water onto the elevator machine room floor., need to repair air conditioning unit |