Inspection
Inspection Details
Equipment ID
12771
12771
Inspection Date
2/6/2019
2/6/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
700
700
Slide
Governor Rope Pull
Door Closing Force
23/22
23/22
External ID
89fb3785-f204-467d-828c-a8ca6e1d6171
89fb3785-f204-467d-828c-a8ca6e1d6171
Location
Wire Works Lofts
1445 S 18TH ST, SAINT LOUIS, MO
1445 S 18TH ST, SAINT LOUIS, MO
Owner
Wire Works in the Square LP
1445 S 18TH ST, SAINT LOUIS, MO 63104-2550
1445 S 18TH ST, SAINT LOUIS, MO 63104-2550
Billing
Attn: Wire Work Lofts in the Square LP
1445 S 18TH ST, SAINT LOUIS, MO 63104-2550
1445 S 18TH ST, SAINT LOUIS, MO 63104-2550
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Phone volume is way too low in cab. Repair. | 2/6/2019 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 2/17/2021 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 6/4/2021 | |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Replace the missing top floor pick up rollers. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit lighting shall be operational. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit shall be kept clean. Clean the pit. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. (Currently no dial tone) | 7/29/2021 | |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | The pit shall be kept clean. Remove excess debris. | 11/8/2023 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Battery lowering shall work. Take corrective action as needed. | 12/11/2023 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | There are no lights in the machine room. Provide code compliant lighting. |