Inspection
Inspection Details
Equipment ID
588
588
Inspection Date
1/28/2019
1/28/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Ronnie Morris
Ronnie Morris
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
7ae70e4e-91f3-4095-a091-10e882e27490
7ae70e4e-91f3-4095-a091-10e882e27490
Location
National Health Care
13995 CLAYTON RD, TOWN AND COUNTRY, MO
13995 CLAYTON RD, TOWN AND COUNTRY, MO
Owner
National Health Care
13995 CLAYTON RD, TOWN AND COUNTRY, MO 63017-8400
13995 CLAYTON RD, TOWN AND COUNTRY, MO 63017-8400
Billing
Attn: National Health Care
13995 CLAYTON RD, TOWN AND COUNTRY, MO 63017-8400
13995 CLAYTON RD, TOWN AND COUNTRY, MO 63017-8400
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This unit is equipped with an overspeed valve that is due for a category 5 test. | 1/19/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 1/19/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and maintenance charts are missing. | 2/16/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | The monthly fire service testing chart shall be maintained. | 2/16/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/16/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly. The log is not being filled out. | 5/25/2023 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | No | No | The third floor door closer spring shall be repaired or replaced. | 5/25/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept free of dirt, oil, and debris. | 5/25/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/25/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall be operational. | 2/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The in car stop switch shall be clearly and permanently marked "STOP" and shall indicate the stop and run positions. Note: The car operating panel keyed stop switch bezel is missing and shall be replaced. | 2/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Horizontally sliding doors of automatic-operation elevators shall be provided with door closers arranged to close and open door automatically. Note: The door closer at the top landing is not working and shall be repaired or replaced. | 2/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fire service phase one key-switch bezel shall be legible. | 2/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fire service phase two key-switch bezel shall be legible. | 2/10/2026 |