Inspection
Inspection Details
Equipment ID
20115
20115
Inspection Date
7/13/2026
7/13/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Relief Valve Pressure
440
440
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
20
20
External ID
9d0cd2ad-db63-4f0c-ae24-47cb2640fc21
9d0cd2ad-db63-4f0c-ae24-47cb2640fc21
Location
Cass Medical Center
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
Owner
Attn: Teresa Cox
Cass Regional Medical Center
2800 E Rock Haven Rd, Harrisonville, MO 64701
Phone: (816) 380-3474 Ext: 4099
Email: tcox@cassregional.org
Cass Regional Medical Center
2800 E Rock Haven Rd, Harrisonville, MO 64701
Phone: (816) 380-3474 Ext: 4099
Email: tcox@cassregional.org
Billing
Attn: Rusty Randall
Cass Regional Medical Center
2800 E Rock Haven Rd, Harrisonville, MO 64701
Phone: (816) 887-0734
Email: rrandall@cassregional.org
Cass Regional Medical Center
2800 E Rock Haven Rd, Harrisonville, MO 64701
Phone: (816) 887-0734
Email: rrandall@cassregional.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | All elevators on EP Generator. Could not test Power Transfer due to surgery schedules. Must Re-reschedule EP Transfer test. | 7/28/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power not tested | 3/7/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | unable to test emg. power at time of insp. | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | emg power illumination lt not working | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone not functioning. No outside line must Reinspect. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power Operation and Transfer Switch could not ne witnessed on the day selected for the annual inspection. Must re-schedule test. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | illumination lt didnt work | 9/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone wasnt answeredin the allotted time an when it was thy couldt idenify the proper elev. | 3/11/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | no emg power indicator lt.at designated floor | 9/12/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 9/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone |