Inspection
Inspection Details
Equipment ID
11775
11775
Inspection Date
1/29/2019
1/29/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Matthew Martin
Matthew Martin
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
21F/19R
21F/19R
External ID
59460457-2c38-45ab-a662-c6e789f2ccf3
59460457-2c38-45ab-a662-c6e789f2ccf3
Location
Herculaneum High School
1 BLACK CAT DR, HERCULANEUM, MO
Phone: (222) 222-2222
Email: sjarnagin@dunklin.k12.mo.us
1 BLACK CAT DR, HERCULANEUM, MO
Phone: (222) 222-2222
Email: sjarnagin@dunklin.k12.mo.us
Owner
Attn: Sherry Jarnagin
Dunklin R-5 School District
600 BARCLAY ST, HERCULANEUM, MO 63048
Phone: (636) 479-5200 Ext: 1003
Email: sjarnagin@dunklin.k12.mo.us
Dunklin R-5 School District
600 BARCLAY ST, HERCULANEUM, MO 63048
Phone: (636) 479-5200 Ext: 1003
Email: sjarnagin@dunklin.k12.mo.us
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/10/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Battery lowering shall be operational. | 11/4/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The battery lowering unit was removed. This is not permitted per the Missouri AHJ. Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. Additionally, per A17.1-2016 - Item 8.6.1.7.5 states: "When any device on which the safety of users is dependent is installed that is not specifically covered in section 8.6, it shall be inspected and tested in accordance with the requirements of the manufacturer's or the altering company's procedures (see 8.6.1.6.1 and 8.7.1.2). Documentation that contains the testing procedures of these devices shall remain with the equipment and be available in the on-site documentation (see 8.6.1.2.2). The removal or disabling of such devices shall be considered an alteration and shall comply with 8.7.1.2. | 11/4/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The battery lowering unit was removed. This is not permitted per the Missouri AHJ. Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. Additionally, per A17.1-2016 - Item 8.6.1.7.5 states: "When any device on which the safety of users is dependent is installed that is not specifically covered in section 8.6, it shall be inspected and tested in accordance with the requirements of the manufacturer's or the altering company's procedures (see 8.6.1.6.1 and 8.7.1.2). Documentation that contains the testing procedures of these devices shall remain with the equipment and be available in the on-site documentation (see 8.6.1.2.2). The removal or disabling of such devices shall be considered an alteration and shall comply with 8.7.1.2. | 9/25/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The battery lowering unit was removed. This is not permitted per the Missouri AHJ. Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. Additionally, per A17.1-2016 - Item 8.6.1.7.5 states: "When any device on which the safety of users is dependent is installed that is not specifically covered in section 8.6, it shall be inspected and tested in accordance with the requirements of the manufacturer's or the altering company's procedures (see 8.6.1.6.1 and 8.7.1.2). Documentation that contains the testing procedures of these devices shall remain with the equipment and be available in the on-site documentation (see 8.6.1.2.2). The removal or disabling of such devices shall be considered an alteration and shall comply with 8.7.1.2. | 4/12/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 9/11/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The battery lowering unit was removed. This is not permitted per the Missouri AHJ. Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. Additionally, per A17.1-2016 - Item 8.6.1.7.5 states: "When any device on which the safety of users is dependent is installed that is not specifically covered in section 8.6, it shall be inspected and tested in accordance with the requirements of the manufacturer's or the altering company's procedures (see 8.6.1.6.1 and 8.7.1.2). Documentation that contains the testing procedures of these devices shall remain with the equipment and be available in the on-site documentation (see 8.6.1.2.2). The removal or disabling of such devices shall be considered an alteration and shall comply with 8.7.1.2. | 6/17/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2025 |